Pneumatic fluorine lined control valves consist of a fluorine lined body assembly and a linear pneumatic multi-spring diaphragm actuator. The pneumatic actuator has two driving modes: forward and reverse. As the air supply pressure increases, the actuator extends from the diaphragm chamber. This is called forward drive and works with the valve body assembly to form a seal. As the air supply pressure blows, the push rod retracts into the membrane chamber.
The pneumatic fluorine lined control valve is a corrosion resistant straight through single seated control valve. The inner wall in contact with the fluid and the valve assembly take high pressure injection molding process. Fluorine lined mastering valve has corrosion lining. Aging resistant polyperfluoroethylene. Propylene (F46) sealed with PTFE bellows. Pneumatic control valve is widely used to master acid, alkali and other strong corrosive media, volatile gases and liquids.
Pneumatic fluorine lined control valve installation procedures
1, check whether the machine parts are damaged or loose. Valve strength, sealing, leakage should be tested.
2、Pipes need to be flushed and valves need to be flushed before installation. The entrance must have enough straight pipe and equipped with a filter. Valve body and pipe flange connection must be coaxial.
3、Personnel and equipment are required at the installation site. Think about the easy driving and dismantling. About the component or vibration, please use the support frame.
5、Medium flow direction must be the same as valve body flow direction. The arrow at the top points to the same direction. The gas source must be dry and oil-free. The valve should be used in the place where the condition temperature is -20?+55℃.
6, in order to make the automatic control system failure or detection of the valve, can still be continuous production, need to add a bypass valve. Bypass valve flow characteristics and distance must be matched with the original valve selection.
7, regulating valve packing seal is a protective secondary seal. If the bellows is damaged, it can not be used as a packing seal valve. Must take measures to repair or replace the bellows. After replacing the bellows, the spool assembly must be strict no leakage, certified before use.